Our products include various types of doors:
-
Fire rated and non fire rated hinged doors.
-
Sound proof hinged doors.
-
X-Ray resisting hinged doors.
-
Security hinged doors.
-
Hinged doors for medical & pharmaceutical uses.
-
Access Doors.
-
Fire rated and non fire rated sliding doors
-
Fire rated wooden hinged doors.
-
Hinged doors with louvers.
Fire rated opening
Requirements
-
Fire door must have a label attached.
-
Fire door must be self-latching
-
Fire door preferred to be self-closer.
-
If a fire door is held open; it must be equipped with a listed heat responsive device, fusible link or a smoke detection device.
-
Fire door must be free of any obstruction which could prevent the door from operating property i.e. wedge door stops, chains, hook backs, floor holder.
-
Only fire rated door hardware shall be used.
-
Fire door must have steel bearing type hinges.
-
Doors swinging in pairs that require astragals shall have at least one overlapping astragals. Pairs of door within a means of egress shall not be equipped with an astragal that inhibits the free use of either leaf. A coordinator or open back strike should be used to ensure proper closing.
-
- Fire doors with glass lights:
-
- The glass frame and glazing bead must be metal
-
- The glass must be wire glass not less than 0.25 inch thick.
-
- Maximum allowable glass area:
-
- 1.5- hour 100 sq. in. per door leaf
-
- 3⁄4 hour 1296 sq.in.per light
-
- Fire doors with fusible link louvers
-
- Only listed louver can be used.
-
- Louvers can be furnished in 1 1⁄2 hour
-
- Maximum louver size is 24” X 24”
-